MGD11 Series
Refrigerant sensor
Refrigerant sensor
The MGD11 series gas sensor module adopts the NDIR gas measurement principle and combines a gold-plated gas chamber with a high-precision sampling circuit. It has built-in temperature compensation and self-calibration functions. It can accurately measure the gas concentration of R32, R454B, R410A in the environment. It has long service life, high measurement accuracy, It has the advantages of good gas selectivity and stable performance.
Measuring refrigerant type
R32/R410A/R454B/R290(Different refrigerant requirements can be customized)
Measurement principle
NDIR(Non-dispersive infrared gas analysis technique)
Performance
Measuring range
0~25%LFL
Measurement accuracy
±2.5%LFL
Warm-up time
Operation takes about 5 s, reaching performance in about 5min
Response time
≤ 20 seconds, test according to the UL 60335-2-40 annex LL.3DV
Power supply
3.8V~5.5V
Working current
Average ≤88mA, typical; peak ≤ 95mA
leakage threshold
10.0%LFL
Output mode
RS485@Modbus-RTU output
Overall dimensions (L×W×H)
52.38mm×63.44mm×18.3mm(L×W×H)
Waterproof and dustproof grade
IP54
Environment
Operating temperature
-40℃~85℃
Operating humidity range
0~100%RH, condensing
Working pressure
60~120kPa
Storage temperature range
-40℃~85℃
Storage humidity range
0~95%RH, non-condensing